【Unique High-Capacity Side Blowing Solution】
The only high-capacity (8-12HP) side-blowing option — perfect where top discharge is not feasible.
【Dual-Fan Side Blowing】
Dual-fan side blowing design handles 8-12HP heat rejection efficiently.
【Enlarged Body for 10-12HP】
100C/120C models use larger chassis (1510×560×1760mm) for enhanced heat exchange.
【Panasonic Large-Displacement Compressor】
Same Panasonic 3CC-series compressors as U-type, now in side-blow configuration.
| Panasonic Refrigeration Fixed Frequency 8-12HP Side Blowing Bellows Integrated Unit Technical Parameters (R404A) | |||||
|
Unit Model |
CAM31P01-080C |
CAM31P01-100C |
CAM31P01-120C |
||
|
Power Supply |
3PH, 380V/50Hz |
||||
|
Nominal Power |
8HP |
10HP |
12HP |
||
|
Maximum Operating Current of the Unit |
22.6A |
27.5A |
35.5A |
||
|
Refrigerant |
R404A |
||||
|
Evap. Temp |
-30-+10℃ |
||||
|
Ambient Temp |
-15-+48℃ |
||||
|
Compressor |
Model |
3CC137LA0M |
3CC171LA0M |
3CC205LA0M |
|
|
Cooling Method |
Electronic expansion valve auxiliary liquid spray cooling |
||||
|
Crankcase Heater |
PTC |
||||
|
Refrigeration Oil |
Type |
FV68S, ester oil |
|||
|
Charge Quantity |
2.5L |
2.5L |
2.5L |
||
|
Condenser |
Number of Fans |
2 |
2 |
2 |
|
|
Fan Blade Diameter |
500 mm |
550 mm |
550 mm |
||
|
Fan Power |
160W*2 |
600W*2 |
600W*2 |
||
|
Heat Exchange Area |
97㎡ |
128㎡ |
143㎡ |
||
|
Structure and Material |
mm internal thread copper tube + hydrophilic aluminum foil, U-type. |
||||
|
System Components |
Oil Separator |
Y |
Y |
Y |
|
|
Gas-liquid Separator |
N |
Y |
Y |
||
|
Receiver |
10L |
16L |
16L |
||
|
Sight Glass |
Y |
Y |
Y |
||
|
Dry Filter |
Y |
Y |
Y |
||
|
High and Low Pressure Gauge |
Y |
Y |
Y |
||
|
High and Low Pressure Controller |
Saginomiya, automatic reset, high pressure 30 bar protection. |
||||
|
Electrical Control |
Circuit Breaker |
CHINT |
|||
|
AC Contactor |
Schneider, LC1D series. |
||||
|
Control Board |
Phase loss and phase error, overcurrent/transformer detection, exhaust temperature protection + liquid injection electronic expansion valve control, condensing fan speed regulation, fault code display, RS485 communication, etc. |
||||
|
Valve Size |
Liquid pipe 5/8, suction pipe 7/8 |
Liquid pipe 5/8, suction pipe 1-1/8 |
|||
|
Outer Dimensions |
1155*500*1480 mm |
1510*560*1760 mm |
|||
|
Unit Weight |
205 kg |
210 kg |
215 kg |
||
|
Unit Operating Noise @1m |
63 dB |
66 dB |
68 dB |
||
|
Recommended Wiring Capacity |
6mm2 |
10mm2 |
10mm2 |
||
|
Cooling Capacity |
Evaporation Temperature |
Ambient temperature +38℃, subcooling temperature 0K, suction temperature +5℃. |
|||
|
-20 |
9050 |
11400 |
13100 |
||
|
-15 |
11000 |
13700 |
15800 |
||
|
-10 |
13200 |
16300 |
18800 |
||
|
-5 |
16000 |
19800 |
22900 |
||
|
0 |
19500 |
24100 |
27800 |
||
|
5 |
23400 |
28900 |
33400 |
||
|
10 |
28500 |
35200 |
40700 |
||
This series includes 3 models:
• CAM31P01-080C — 8HP, 205 kg
• CAM31P01-100C — 10HP, 210 kg
• CAM31P01-120C — 12HP, 215 kg
• Plant rooms with height restrictions — First choice where top discharge is not possible
• Supermarket back rooms / basements — Basement plant rooms of large supermarkets
• Food processing workshops — Constrained indoor installations
• Renovation projects — Retrofits with existing space constraints
• Voltage: 380V customizable
• Refrigerant: R404A / R449A / R448A
• Remote monitoring: Optional
• Anti-corrosion: Customizable